Skip navigation links

Package org.lsst.ccs.subsystem.airwatch.main

The main package for the AirWatch subsystem.

See: Description

Package org.lsst.ccs.subsystem.airwatch.main Description

The main package for the AirWatch subsystem.

At subsystem start-up a periodic task is started to read the particle-counter instruments with at regular intervals (fixed period) and send the data to the trending subsystem. Only new data, accumulated since the last time data was read, is posted for each instrument.

A stop command will have no effect on a readout in progress but will cancel any further readouts.

An abort command will interrupt a readout in progress. Subsequent readouts will still occur if they are scheduled. An abort is a no-op if no readout is in progress. When a readout is interrupted a given instrument will either have had its new data sent to trending and its last-data-time updated, or neither.

Query commands will execute without delay, though they might not show concurrent changes in instrument state being made by action commands or the readout task.

Action commands that mutate instrument state will be rejected if a readout is in progress, otherwise they'll run without delay. Readout may take several minutes so it seems better to reject conflicting commands right away so that the operators can abort the current readout if they want.

If the readout task encounters an instrument I/O error it will raise an alert of severity WARNING whose ID is "InstrumentIO". The cause string will be the instrument location plus the message from the HardwareException that was thrown as a result of the problem. Operators may wish to abort and disable readout for the offending channel. Before clearing the alert the operators may attempt to re-enable the instrument or decide to leave it disabled. In either case the alert may be cleared without further checks by the subsystem.

Lighthouse instruments
The instrument contains a table of location names which should be the same as the list of known locations obtained from the subsystem configuration. That way changing the instrument's current location can be done just by writing the index number + 1 to the current-location register.

Those Lighthouse hand-held models allow only uppercase letters to be entered for location names, so case is ignored when comparing the names with configured location names for all models.

The enable and read operations sync a hand-held instrument's clock with that of the computer.

Skip navigation links